| Main Parameters | |
|---|---|
| Capacity (Ah) | 100 |
| Scalability | Max. 64 pcs pack (327kWh) in parallel (Max. 32 pcs no external setup) |
| Nominal Voltage (V) | 51.2 |
| Operating Voltage(V) | 43.2~57.6 |
| Nominal Energy (kWh) | 5.12 |
| Charge/Discharge Current(A) | Recommend 50 |
| Recommend Depth of Discharge | 90% |
| Dimension (W/H/D, mm) | 440*133*540 |
| Weight Approximate(kg) | 45 |
| Operating Temperature | Charge: 0~55℃ ( Optional heating: -20℃~55℃ ), Discharge: -20℃~55℃ |
| Cycle Life | ≥6000 (25℃±2℃, 0.5C/0.5C, 90%DOD, 70%EOL) |
| Certification | UN38.3, IEC62619, CE, UK, VDE2510-50, CEI 0-21, FCC, UL1973, UL9540A |
This battery pack has a nominal capacity of 100Ah and a nominal voltage of 51.2V, delivering an energy capacity of 5.12 kWh.
It supports parallel scalability up to a maximum of 64 packs, providing a total storage capacity of 327kWh. Parallel systems up to 32 packs do not require an external setup.
The recommended depth of discharge (DOD) is 90%. Under normal conditions (25℃±2℃, 0.5C/0.5C, 90% DOD, to 70% EOL), the battery delivers a cycle life of 6000 cycles or more.
The standard charging temperature range is 0℃ to 55℃, with an optional heating feature supporting charging from -20℃ to 55℃. The discharging temperature range is -20℃ to 55℃.
The battery holds a comprehensive list of international certifications, including UN38.3, IEC62619, CE, UK, VDE2510-50, CEI 0-21, FCC, UL1973, and UL9540A.